45 TON INDUSTRIAL RENTAL AC UNIT WITH HEAT & DH MODES
INFORMATION
Additional Technical Documents
UNIT FEATURES
- Direct drive High Static plenum fan with 10hp TEFC motor
- Maximum rated static pressure of 6.5 in-wg
- Rated air flow of 6000 cfm with 100% Outside Air
- Air flow range of 3,200 – 8,000 cfm
- Stainless steel hardware
- 2 Independent stages of dehumidification
- 2 independent stages of reheat, each stage can be isolated
PACKAGE FEATURES
- Phase monitor and Incorrect phase indicator light (red)
- Circuit Breakers on all motors
- Blower VFD with inline starter and bypass switch
- Speed Potentiometer for Blower VFD to adjust speed from 40Hz to 78Hz
- Full tubular rental frame with fork pockets & tie-down points
- Hot-dipped galvanized
- Overhead certified lift frame
- Entering and leaving air temperature sensors
- Duct Doors factory installed for all supply/return connections
- Quiet operation
- Manual (hand) option for running stages 1 & 2
- Marked Center of Gravity
- Separate control panel for High Voltage components, 100 V components and customer controls
- Easy to operate PLC controller. Can be controlled via entering air conditions, leaving air conditions, or remotely
- Installed Emergency Stop
- Airflow meter
- Installed static pressure gauge
SPECIFICATIONS
GENERAL | |
---|---|
Duct/Hose Connections | (2) 20” Supply / (2) x 20” Return |
Unit Dimensions | 88”L x 96”W x 99.75”H |
Unit Ship Weight | 7,200 lbs |
Filter Size | (2) 25 x 28 x 2 and (1) 20 x 28 x 2 |
ELECTRICAL | |
---|---|
USA Certification | ETL Certified (in accordance with UL1995) |
Canadian Certification | CSA Certified No 236 STD22.2 |
Single Point Power Supply | 460V/3PH/60HZ |
Dehumidification Amps | 82.0 A |
Blower Fan Amps | 11.6 A |
Unit Minimum Circuit Ampacity | 90.0 A |
Unit MFS / MOCP | 125 A |
Connections | Single point Series 16 Cam-Lok connections |